Specifications:
Description:
Solid or stranded plain copper conductors, PVC insulated, laid up with bare
copper earth wire, PVC sheathed overall.
Application:
For the wiring of:
Under-plaster wiring Roof wiring Under-floor wiring
Specification: SANS 1507/2002
Voltage Rating 300/500 V
Temperature Range -10°C to 70°C
Sheath colours Black and white
Core colours 2 core - black and red
3 core - blue, red and yellow
4 core - black, blue, red and yellow
Packaging:
Packaging 100 meter
Shrink-wrapped coils
Also available on 1000 meter Wooden drums
Technical Information
CABLE SIZE
# |
CONDUCTOR
TYPE |
NOMINAL
OVERALL
DIAMETER |
CURRENT
RATING
NOTE 1 |
VOLT DROP
NOTE 1 |
APPROX. CABLE
WEIGHT
MASS PER
100M COIL |
(mm2) |
(MAIN) |
(EARTH) |
(mm) |
(A) |
(MV/A/M) |
(kg) |
1.0 |
1/1.5 |
1/1.5 |
7.9 x 4.3 |
15 |
44 |
6.76 |
1.5 |
1/1.38 |
1/1.15 |
8.8 x 4.8 |
19 |
29 |
8.33 |
2.5 |
1/1.78 |
1/1.38 |
10.4 x 5.6 |
27 |
18 |
11.7 |
4.0 |
7/0.86 |
1/1.38 |
12.2 x 6.2 |
36 |
11 |
18.3 |
6.0 |
7/1.04 |
1/1.78 |
13.7 x 7.2 |
46 |
7.3 |
23.4 |
10.0 |
7/1.38 |
7/0.86 |
17.2 x 8.6 |
63 |
4.4 |
37.1 |
16.0 |
7/1.72 |
7/1.04 |
20.0 x 9.8 |
85 |
2.8 |
52.0 |
Note 1: These ratings are for 2 cables
single phase AC or DC clipped direct as per SANS 0142 table 6.3
# Conductors of 4mm2 and over are stranded
|