Distributor of Electrical Cable/Wire, Electrical Equipment, O-line Support Systems, Network Equipment and Cabling

 

Specifications:

Description:
Plain Annealed copper conductors, PVC insulated, PVC Bedded, Galvanised Steel Wire Armour with Earth Continuity Conductors in the armour, PVC Sheath.

Application:
These cables may be used for main power distribution in general industries, houses and commercial buildings where the concentric earth eliminates the need for a supplementary earth continuity conductor.

Specification: SANS 1507/2002
Voltage Rating: 600/1000 V
Sheath colours Black with coloured stripe depending on insulation material used in cable
Core colours 2 core – Black and red
3 core – Red, yellow and blue
4 core – Red, yellow, blue and black
7 core – Red, yellow, blue, black, violet, brown and orange

Packaging:
Packaging 300 & 500 meter Wooden drums


Technical Information

CABLE SIZE APPROX CURRENT RATING VOLT DROP APPROX.CABLE WEIGHT
OVERALL  Note 1 MASS PER 100M
DIAMETER    
(mm2) (mm2) (mm) (Amps) (MV/AM) (Kg)
    2C 3C 4C 7C 2C 3,4,&7C   2C 3C 4C 7C
1.5 1 14 14 15 17 21 18 29  39 45 49 63
2.5 1.5 15 15 16 18 28 25 18 45 50 58 76
4 2.5 17 17 19 22 38 33 11 58 66 75 102
6 4 18 19 20 23 49 42 7.3 69 79 91 123
10 6 20 21 23 - 67 58 4.4 87 99 116 -
16 10 18 20 22 - 89 77 2.8 78 106 132 -
25 16 - 27 28 - 118 102 1.75 - 169 198 -
35 16 - 28 31 - 145 125 1.25 - 227 244 -
50 25 - 32 37 - 175 151 0.93 - 296 330 -
70 35 - 36 40 - 222 192 0.63 - 372 464 -
95 50 - 40 45 - 269 231 0.46 - 505 614 -
120 70 - 42 47 - 310 267 0.36 - 589 731 -
150 70 - 46 53 - 356 306 0.29 - 711 953  
185 95 - 51 58 - 405 248 0.23 - 895 1136 -
240 120 - 57 64 - 476 409 0.18 - 1108 1413 -
300 150 - 62 70   547 469 0.145 - 1334 1704 -

 

Note 1: These ratings are per SANS 0142 table 6.4


 



 
  Page last updated - 2009/05/09